Integrated Boost Converter – 1500V

1500V Integrated Boost Converter

2500kW/3150kw/3450kW

Key Features

  • Three-level topology, maximum efficiency 99%.
  • High protection level (IP54, C5 optional).
  • DC side 250kA short-circuit current breaking capacity
  • Four quadrant operation, with battery charge and discharge management function
  • It has the functions of primary frequency modulation and fast dispatching of source network load

Specs

Category:

Description

1500V Integrated Boost Converter

2500kW/3150kw/3450kW

Key Features

  • Three-level topology, maximum efficiency 99%.
  • High protection level (IP54, C5 optional).
  • DC side 250kA short-circuit current breaking capacity
  • Four quadrant operation, with battery charge and discharge management function
  • It has the functions of primary frequency modulation and fast dispatching of source network load

Technical Parameters

System type 2500kW 3150kW 3450kW
DC Side Data
DC voltage range 800~1500V 875~1500V 1000~1500V
Maximum DC current 1744A*2 2010A*2 1935*2
AC Side Data
AC side rated power 1250kW*2 1575kW*2 1725kW*2
AC side maximum power 1375kVA*2 1732kVA*2 1897kVA*2
Rated AC current 1312A*2 1516A*2 1443A*2
Maximum AC current 1443A*2 1667A*2 1587A*2
Rated AC voltage 550Vac,3W+PE 600Vac,3W+PE 690Vac,3W+PE
AC voltage range 550Vac,(-15%~+15%) 600Vac,(-15%~+15%) 690Vac,(-15%~+15%)
Max.THD of current <3%(at nominal power)
DC component <0.5%(at nominal power)
Power factor > 0.99
Adjustable power factor 1 leading ~ 1 lagging
Nominal grid frequency 50/60 Hz
Grid frequency range ±5Hz
Isolation method Transformer Isolation
Transformer Data
Rated power 2500kVA 3150kVA 3450kVA
Maximum power 2750kVA 3464kVA 3794kVA
Voltage ratio 0.55kV/6~35kV 0.6kV/6~35kV 0.69kV/6~35kV
Bank type Dy11
General Data
Dimensions of unit (W * H * D) 6058×2896×2438mm
Weight of unit 15 T 16 T 17 T
Degree of protection IP54 / NEMA 3R
Operating temperature range -30 ~+60°C(>50°Cderating)
Relative humidity 0 ~ 95% (non-condensing)
Max. working altitude 3000m
Cooling concept of PCS chamber PCS Temperature controlled forced air cooling
Fire suppression system of battery unit Heptafluoropropane/Perfluorohexanone
Communication interfaces RS485 / CAN 2.0 / Ethernet
Communication protocols General:Modbus RTU,Modbus TCP,IEC 104
Optional:IEC 61850
Compliance CE,IEC 61000,IEC 62477-1:2012,IEC 61727,IEC 62116

 

 

Reviews

There are no reviews yet.